ANTSPACE HK3 V6

产品特点:
  • Specification Details For ANTSPACE HK3 V6Product OverviewModelANTSPACE HK3 V6Dimensions (L*W*H) (mm)6058*2438*2896Miner Capacity210 units -S19 Hyd. Series minerContainer CertificationChina Classification Society CertificationSafety CertificationNFPA 79:2021UL 508A:2018 R8.21CSA C22.2 No. 14-18ANSI/I
产品详情

Specification Details For ANTSPACE HK3 V6

Product Overview
Model ANTSPACE HK3 V6
Dimensions (L*W*H) (mm) 6058*2438*2896
Miner Capacity 210 units -S19 Hyd. Series miner
Container Certification China Classification Society Certification
Safety Certification

NFPA 79:2021
UL 508A:2018 R8.21
CSA C22.2 No. 14-18
ANSI/ISO 12100:2012
IEC 60204 Ed 5.1 2009

Operating Power(kW) 1047~1050
PUE(Power Usage Effectiveness) 1.022(Excluding cooling tower)/1.036(Including cooling tower)
Input Voltage and Frequency

400V±5% 50/60Hz

Detailed Characteristics
Shipping Weight(T) 8
Operating Weight (T) 12
Main Switch of Power Distribution Cabinets(A) 1200
Rated Current(A) 952
Standard Power(kW) 1049
Maximum Power(kW) 1050
Rated Current per Miner(A) 10
Inlet Cable The inlet cables can withstand high-voltage of above 600V, with the following requirements per phase:
L1 single core cable 600kcMil(300mm²)x4
L2 single core cable 600kcMil(300mm²)x4
L3 single core cable 600kcMil(300mm²)x4
N Single-core cable 600kcMil(300mm²)x4
PE single-core cable 500kcMil(240mm²)x2
Connection Interface(Cooling Tower) DN100(ISO2852 PN16)
Connection Interface(Plate Heat Exchage Interface) DN100(GB/T 9119-2010 PN16 DN100)
Flow Rate(m³/h) >85
Quantity of ANTSPACE powered by one 2500kVA Transformer 2

Specification Details For Dry-Wet Towers

Product Overview
Type Dry-Wet Tower Container Type (DWT-C)
Dimensions(L*W*H)(mm) 6058*2438*2896
Heat Dissipation Capacity(kW) 1200
Outlet Temperature @ 28℃ Wet Bulb Temperature 35℃
Container Certification China Classification Society Certification
Safety Certification

NFPA 79:2021
UL 508A:2018 R8.21
CSA C22.2 No. 14-18
ANSI/ISO 12100:2012
IEC 60204 Ed 5.1 2009

Operating Power(kW) 14~28
Motor Rated Voltage and Frequency

400V±5% 50/60Hz

Detailed Characteristics
Shipping Weight(T) 7
Operating Weight(T) 13
Connection Interface(Container) DN125(GB/T 9119-2010 PN16 DN125)
Water Resupply Pipe Interface DN40(Internal thread)
Drain Pipe Interface DN65(Internal thread)
Noise Level @25℃, 16m 70dBA
Water Consumption(m³/h) 1~1.3m³/h

Specification Details For Plate Heat Exchanger

Product Overview
Type Plate Heat Exchanger (PHE)
Dimensions(L*W*H)(mm) 775*454*1090
Material TI
Detailed Characteristics
Shipping Weight(KG) 360
Operating Weight(KG) 440
Connection Interface(Container) DN100(GB/T 9119-2010 PN16 DN100)
External circulation supply liquid temperature (℃) 0~30
External circulation flow rate (m³/h) 33~110
Internal circulation flow rate (m³/h) 100

Specification Details For Dry Cooler Towers

Product Overview
Type Dry Cooler Towers Container Type (DCT-C)
Number 2
Dimensions(L*W*H)(mm) 6058*2438*2896
Outlet Temperature @ 30℃ ambient temperature 35℃
Container Certification China Classification Society Certification
Operating Power(kW)

20~32

Motor Rated Voltage and Frequency 400V±5% 50/60Hz
Detailed Characteristics
Shipping Weight(T) 6
Operating Weight(T) 8
Connection Interface(Container) DN125(GB/T 9119-2010 PN16 DN125)
Water Resupply Pipe Interface DN10(Tapered tube)
Noise Level @25℃, 16m 65dBA
Pipe materials 304 stainless steel

| Points For Attention


 

1 Cooling tower is better located on flat level ground, horizontal degree (±1 degree).
2 The ground below said ANTSPACE units must be well-hardened and stable enough to always withstand
3 Buyers of the ANTSPACE should prepare a 20t crane, assemble suitable tools and manpower, and arrange all required logistics if an ANTSPACE order is to be delivered to the site of opera4tion.
4 Peripheral items such as stairs, transformers, cables, bridge racks and cable distribution boxes are not
5 If you plan to store ANTSPACE units vertically on top of one another, please advise the Bitmain sales' team
6

Leave at least 2 meters of air inlet space around the cooling tower

7 Operating elevation: ≤2000m. If elevation is greater than 1000 meters and a 2500kVA transformer is being used, the number of Antminer units installed in one ANTSPACE unit must be decreased.
8 Operating temperature: -25°C to 40°C. Operating humidity: 10%RH to 90%RH. The ambient temperature requirement in high humidity areas is not higher than 40 °C. When the ambient temperature is <0 °C, the inlet and outlet blinds should be closed and the   internal heating should be >0 °C before the mining
9 The ambient temperature of the ANTSPACE does not represent the ambient temperature of the mining machine.